Description:
BACOGA BCG® SR Reiniger is designed to remove limescale, rust, and sludge deposits from pipe systems, improving system efficiency and reducing energy consumption. It is suitable for use on various materials commonly found in thermal construction, including copper, steel, stainless steel, aluminum, and plastic.
SR Reiniger fluid effectively cleans pipe systems, enhancing system efficiency and reducing energy consumption. Its use is particularly recommended during modernization or when cleaning and optimizing old heating systems. It can be applied to materials commonly used in thermal construction, such as copper, steel, stainless steel, aluminum, and plastic. No special tools are required to fill the BCG SR Reiniger fluid into a heating system.
BACOGA BCG SR Reiniger User Instructions:
Note: Rinse heavily soiled systems thoroughly beforehand using plenty of water.
- Empty approximately 20 liters of system water from the system.
- Close the filling/draining tap.
- Drain the filling hose of water.
- Fill the SR Reiniger fluid into the hose using a funnel.
- Connect the hose to the tap.
- Open the filling/draining tap.
- Open the tap. SR Reiniger fluid is now pressed into the heating circuit.
- Close the tap and the fill/drain tap.
- Disconnect the hose from the tap and empty it.
- Repeat the process until the required amount of SR Reiniger fills the system.
- Fill the heating system to operating pressure.
- Fully open all heating and mixing valves.
- Set the heating system to operating temperature.
- Vent the system.
- SR Reiniger fluid must remain in the plant for 2 - 4 days at an operating temperature of max. 60˚C. Adequate ventilation of the heating system is necessary before filling the SR Reiniger into the system to avoid gas evolution from dissolving limescale deposits.
- Empty the heating system completely and rinse it thoroughly with water.
- Finally, refill the heating system with fresh water and add BCG SK Korrosion protection if necessary.
Note: It's recommended to consult an authorized plumber before using the product. Keep out of reach of children.
Disposal: See safety data sheet.
Mixing ratio: 1 liter of BCG SR Reiniger per 200 liters of system water.
Shelf life/Storage: Unopened 5 years from the date of manufacture. Store cool and protected from sunlight.
Note: There must be no additives in the heating system, such as frost and corrosion protection or sealing fluids. The concentration of BCG SK Korrosion must be checked once a year.